- Panels
- Battery cables
- Fusible
- End of line resistors
Primary power supply | Switching source 187-252V AC 50-60 Hz 65W max. |
Backup power supply | 2 batteries 12VDC (up to 5 Ah). Ensures minimum 120 hours duration. |
Number of zones | 4 zones, up to 30 detectors by area. |
Siren outputs | 2 siren outputs 24VDC. Independent and monitored open collector outputs |
Relay outputs | 4 Relay outputs: [VAR%] Alarm output, 1 Fault output and 1 configurable relay outputs. All support 30VDC 3A max. |
End of line resistance | Areas fully monitored by end-of-line resistance (4.7K) |
Auxiliary Output Voltage | 24VDC. Protected by resettable electronic fuse 1.85A |
Protection Index | IP30 |
Temperature | -5ºC~+45ºC |
Material and colour | ABS, colour: White |
Dimensions | 310 x 240 x 80 mm |
Weight | 1,3Kg |
Recommended cable | Fire cable with a minimum section of 1.0mm (18AWG). |